1.1 ,These multi-test methods cover the determination of the oxyhalides—,chlorite, bromate, and chlorate, and bromide, in raw water, finished drinking water and bottled (non-carbonated) water by chemically and electrolytically suppressed ion chromatography. The ranges tested using these test methods for each analyte were as follows:
| , | Range | Sections |
| Test Method A: | , | 8 to 20 |
| ,Chlorite | 5 to 500 µ,g/L | , |
| ,Bromate | 1 to 25 µ,g/L | , |
| ,Bromide | 5 to 250 µ,g/L | , |
| ,Chlorate | 5 to 500 µ,g/L | , |
| , | , | , |
| Test Method B: | , | 21 to 31 |
| ,Chlorite | 20 to 1000 µ,g/L | , |
| ,Bromate | 1 to 30 µ,g/L | , |
| ,Bromide | 20 to 200 µ,g/L | , |
| ,Chlorate | 20 to 1000 µ,g/L | , |